D 244 030 00 | EtherCAT Coupler with integrated digital inputs/outputs
The EtherCAT Couplers from the EK18xx series combine the functionalities of the EK1100 EtherCAT Coupler with standard digital I/Os in one housing. This results in a compact design that is especially suitable for applications with a low number of I/Os. Like the EK1100, the EK18xx coupler can be extended by all EL/ES terminals. The digital I/Os are implemented with a 1-wire technique. The wiring can be implemented without tools using a direct plug-in technique with solid wire conductors or ferrules.
The D 244 030 00 has eight digital inputs and four digital outputs.
| TECHNICAL DATA | D 244 030 00 | 
|---|---|
| Task within EtherCAT system | coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCAT networks | 
| Data transfer medium | Ethernet/EtherCAT cable (min. CAT 5), shielded | 
| Distance between stations | max. 100 m (100BASE-TX) | 
| Number of EtherCAT Terminals | up to 65,534 | 
| Protocol | EtherCAT | 
| Delay | approx. 1 µs | 
| Data transfer rates | 100 Mbaud | 
| Bus interface | 2 x RJ45 | 
| Nominal voltage | 24 V DC (-15 %/+20 %) | 
| Current supply E-bus | 1000 mA | 
| Current consumption from UP | 40 mA + load | 
| Current consumption from US | 100 mA + (∑ E-bus current/4) | 
| Number of inputs | 8 | 
| Specification | EN 61131-2, type 1/3 | 
| “0“ signal voltage | -3…+5 V (EN 61131-2, type 1/3) | 
| “1“ signal voltage | 15…30 V (EN 61131-2, type 3) | 
| Input filter | 3.0 ms | 
| Input current | typ. 3 mA (EN 61131-2, type 3) | 
| Number of outputs | 4 | 
| Load type | ohmic, inductive, lamp load | 
| Max. output current | 0.5 A (short-circuit-proof) per channel | 
| Short circuit current | typ. < 2 A | 
| Reverse voltage protection | yes | 
| Breaking energy | < 150 mJ/channel | 
| Switching times | typ. T ON: 60 µs, T OFF: 300 µs | 
| Electrical isolation | 500 V (power contact/supply voltage/Ethernet), 500 V (E-bus/field potential) | 
| Conductor types | solid wire, stranded wire and ferrule | 
| Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver | 
| Rated cross-section | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² | 
| Operating/storage temperature | -25…+60 °C/-40…+85 °C | 
| Relative humidity | 95 %, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. class/installation pos. | IP 20/variable | 
| Approvals | CE, UL | 
| Related products | |
| EtherCAT Coupler with 8 integrated digital inputs and 4 integrated digital outputs | |
| EtherCAT Coupler with 4 integrated digital inputs and 4 integrated digital outputs | |
| EtherCAT Coupler with 4 integrated digital inputs and 8 integrated digital outputs | |
| EtherCAT Coupler with 8 integrated digital outputs | |
| EtherCAT Coupler with integrated digital standard and safety I/Os | 
You can also find more documentation on the following site